WebSlash ratings (e.g. 480/277V) are only intended for solidly grounded wye systems. Series Ratings . It is possible to enhance the ampere interrupting rating of circuit breakers with a higher rated upstream circuit breaker or with an upstream current-limiting fuse. Although this can allow the use of less expensive downstream circuit WebApplying a slash-rated breaker in such a system may result in complete device failure when a full voltage fault exceeds the circuit breaker rating. This is a violation of Section 240.85, …
Contents Molded-Case Circuit Breakers & Enclosures - Eaton
WebMay 16, 2007 · Slash voltage ratings for circuit breakers are addressed in NEC 240.85 restricting their use to solidly grounded systems where the line-to-ground voltage does not exceed the lower of the two values and the line voltage does not exceed the higher value. Overcurrent protective devices that may be slashed rated include, but are not limited to: grand ittehad facebook
Molded Case Circuit Breaker – Marking and Application Guide
WebJun 15, 2024 · A breaker might be single- or dual-voltage rated. You can use a circuit breaker with a: Single-voltage rating (e.g., 240V or 480V) if the nominal voltage between any two conductors (line-to-neutral or line-to-line) does not exceed the circuit-breaker voltage rating [Sec. 240.85]. WebAug 17, 2024 · These circuit breakers display two voltage markings separated by a slash – some typical markings are 120/240 V, 208Y/120 V, 480Y/277 V, and 480/277 V. The lower figure is the nominal voltage to the ground, and the higher number is the nominal voltage between two ungrounded conductors. Webovercurrent protective device must be utilized. For example, a 480V circuit breaker may have to open an overcurrent at 480V with only one pole, such as might occur when Phase A goes to ground on a 480V, B-phase, corner grounded delta system. The NEC® addresses slash voltage ratings for circuit breakers in 240.86 restricting their use to ... grand iva sector 103 gurgaon